Audit Retrospektif Kinerja Chiller Tanpa Bas: Validasi Data Ultrasonik Portabel Dan Deteksi Anomali Yang Dapat Dijelaskan
Original Full-Text Article
Download published version for reading and archivingAbstract
Chillers in government buildings located in tropical climates often operate without a building automation system (BAS), making performance degradation difficult to detect through routine monitoring. This study reanalyzes the 2024 field measurement dataset for a 500 TR (R134a) water-cooled centrifugal chiller in a city government office without new data collection. The Isolation Forest model interpreted with permutation-based SHAP attribution marks instances of zero flow rate and surrounding reading changes, with residuals against local trends as the primary explanatory feature. Extended flatline segments following zero events are overlooked, complementing rather than replacing manual screening. The marking proportion ranges from 6.2% to 6.5% per session, adhering to a contamination parameter of 0.06. Pipe cross-section examinations restore stable diameters at three locations: 240 mm, 97.7 mm, and 450 mm, correcting a labeling error. Recalculated results show evaporator heat of 825.5 ± 79.7 kW and an actual COP of 3.75 ± 0.36 compared to a design COP of 5.76 at a measured load of 47.2% capacity. The energy balance deviation reaches 11.6%, exceeding the 5% threshold. This imbalance reflects combined uncertainty, with specific power at 0.94 kW/TR and a temperature difference of 1.3 °C, consistent with additional thermal resistance yet to be verified.
Keywords:
Author Biographies
Pusat Pengembangan Sumber Daya Manusia KEBTKE, Daerah Khusus Ibukota Jakarta, Indonesia
Program Studi Teknik Elektro, Fakultas Teknik, Universitas Dian Nusantara, Bekasi, Provinsi Jawa Barat, Indonesia.
How to Cite
This is an open-access article distributed under the terms of the Creative Commons Attribution 4.0 International License .
- Share: You are free to copy, distribute, and transmit the work in any medium or format.
- Adapt: You are free to remix, transform, and build upon the work for any purpose, even commercially.
- Attribution: You must give appropriate credit, provide a link to the license, and indicate if changes were made. You may do so in any reasonable manner, but not in any way that suggests the licensor endorses you or your use.
References
Total: 30 References- Aguilera, J. J., Meesenburg, W., Markussen, W. B., Poulsen, J. L., Zühlsdorf, B., & Elmegaard, B. (2023). Adaptive model-based monitoring of large-scale heat pump prone to evaporator fouling. 0565. https://doi.org/10.18462/IIR.ICR.2023.0565
- AHRI. (2023). AHRI Standard 550/590 (I-P): Performance rating of water-chilling and heat pump water-heating packages using the vapor compression cycle. Air-Conditioning, Heating, and Refrigeration Institute. https://www.thenbs.com/publicationindex/documents/details?Pub=AHRI&DocId=342937
- Almobarek, M. (2024). Most frequent chiller’s faults: An empirical predictive maintenance study. IEOM Society International, USA. https://doi.org/10.46254/NA09.20240193
- ASHRAE. (2016). ANSI/ASHRAE/IES Standard 90.1-2016: Energy standard for buildings except low-rise residential buildings. American Society of Heating, Refrigerating and Air-Conditioning Engineers. www.ashrae.org
- Badan Standardisasi Nasional. (2020). SNI 6390:2020 Konservasi energi sistem tata udara pada bangunan gedung (ICS 91.040.01). Badan Standardisasi Nasional. https://akses-sni.bsn.go.id/dokumen/2020/SNI%206390-2020/#p=1